Voltage Drop Calculator

Single or three phase, AWG or mm² — see if a run stays under the 3 % recommendation.

Updated 2026-10-20 · Based on: NEC Chapter 9 Table 8 and 310.16; DIN VDE 0100-520 for metric.

How to use the Voltage Drop Calculator

  1. Choose copper or aluminum and the wire size.
  2. Enter the one-way length of the run.
  3. Enter the load current and the supply voltage.
  4. Keep the drop under 3 % for branch circuits (5 % total).

Formula

Single phase: Vd = 2 × L × I × R. Three phase: Vd = √3 × L × I × R, with R the resistance per foot (NEC Chapter 9, Table 8, at 75 °C).

Metric: Vd = 2 × L × I ÷ (κ × A), with κ = 56 for copper and 35 for aluminum.

Worked example

With the values preset in the calculator above:

Material
Copper
One-way length
100 ft
Current
20 A
Voltage
120 V
Phase
Single phase
Wire size
12
Voltage drop
7.72 V
Voltage drop (%)
6.43%
Voltage at the load
112.28 V
Result
Over 5 % — use a larger wire

Related guides

Frequently asked questions

What is the voltage drop on 12 AWG at 100 ft and 20 A?

7.72 V on 120 V — 6.43%, too much. 10 AWG gives 4.03%; 8 AWG gets under 3 % (2.55%).

What is an acceptable voltage drop?

The NEC recommends no more than 3 % on a branch circuit and 5 % in total (feeder + branch).

Does voltage drop depend on the breaker?

No — it depends on wire material, size, length and the actual current flowing.

More calculators

All construction calculators →

Estimates only — check quantities with your supplier and local building code before you order.