The smallest wire that carries the current safely and keeps the voltage drop within your limit.

Updated 2026-10-20 · Based on: NEC Chapter 9 Table 8 and 310.16; DIN VDE 0100-520 for metric.

How to use the Wire Size Calculator

  1. Enter the current, the one-way distance and the voltage.
  2. Choose copper or aluminum and single or three phase.
  3. Keep 3 % as the maximum drop.
  4. Use the recommended size — the larger of the ampacity and voltage-drop sizes.

Formula

Ampacity: NEC 310.16 (75 °C column) with the small-conductor limits of 240.4(D): 14 AWG 15 A, 12 AWG 20 A, 10 AWG 30 A copper.

Voltage drop: the smallest size whose drop is under your limit (see the voltage drop calculator).

Worked example

With the values preset in the calculator above:

Material
Copper
One-way distance
100 ft
Current
20 A
Voltage
120 V
Phase
Single phase
Max voltage drop
3 %
Recommended wire size
8 AWG
Minimum for the current
12 AWG
Minimum for voltage drop
8 AWG
Voltage drop (%)
2.55%

Wire size chart (copper, 75 °C)

  • 14 AWG — 15 A
  • 12 AWG — 20 A
  • 10 AWG — 30 A
  • 8 AWG — 50 A
  • 6 AWG — 65 A
  • 4 AWG — 85 A
  • 2 AWG — 115 A
  • 1/0 AWG — 150 A
  • 2/0 AWG — 175 A
  • 4/0 AWG — 230 A

Related guides

Frequently asked questions

What size wire for 20 amps at 100 ft?

12 AWG copper carries 20 A, but at 100 ft on 120 V the drop is too high — the calculator recommends 8 AWG.

What size wire for a 50 amp circuit?

8 AWG copper (6 AWG for long runs or aluminum).

Is this a substitute for an electrician?

No. It follows the NEC tables for typical conditions; ambient temperature, bundling and local code can change the size.